Home  »  Products  »  Linear actuators  »  V Linear actuator

V Linear actuator

V series linear actuators are used when precise linear adjustments are required to control elements in heating, ventilation and air conditioning systems as well as in industrial applications.

V series linear actuators are available with actuating forces of 400 N bis 5000 N and a maximum stroke of 85 N.

The design of the housing made of die-cast aluminium and zinc in combination with permanently lubricated gearing with sintered-bronze bearing bushes ensures their suitability for use in a harsh operating environment. The technical construction mirrors that of series N actuators. End position limit stop is force-dependent. The standard scope of supply includes a limit switch for each end position. These are designed as changeover switches and can also perform supplementary functions such as end position indication or sequential control tasks.

Additional force and auxiliary position switches as well as potentiometers are also available. Fitting a relay makes it possible to control several actuators simultaneously via a common contact. The respective position of the valve is indicated by “Open/closed” markings on one of the columns of the stroke unit in conjunction with the bearing surfaces of the spindle nut. A solid flange is available to mount the actuator. A driver pin is included for connecting the actuator with the threaded spindle.

Details
Back to product overview
[Translate to English:] V Linearantrieb
[Translate to English:] V Linearantrieb

Motor

  • Single-phase AC synchronous motor with permanent magnets, reversible 230 V ± 10%, 50/60 Hz ± 5% (datasheet V)
  • 100% duty cycle as standard
  • Short start/stop times
  • Insulation class B to VDE 0530
  • Synchronous motors maintain speed and positioning time irrespective of the load
  • Tropical insulation
  • Options:
    • Custom voltages
    • Custom frequencies

Gearbox

  • Spur gearing with straight-toothed steel gears
  • Rugged, maintenance-free
  • Permanently lubricated gears
  • Self-lubricating sintered bronze bearings
  • Encapsulated version, operates in any position

Spindle

  • Self-locking
  • “Open/closed” markings indicate position
  • Made of stainless steel

Electrical connection

  • Connection terminals positioned centrally close to cable entry
  • Screw-type terminals
  • Two free slots to retrofit additional force/position switches
  • Retrofitting of extensions possible without any problems through additional PCB terminals
  • Infinitely adjustable control cams
  • Open/close signal
  • Path-dependent limit switch-off
  • One limit switch each for the end positions
  • Options:
    • Additional potential-free switching contacts
    • Electronic position controller ESR-N (integrated in the actuator or external)
    • Potentiometer 200Ω … 10 kΩ

Ambient temperature

  • -15 °C to +60 °C
  • 0 °C to +60 °C when an electronic position controller ESR-N is used
  • Options:
    • Up to +80 °C, duty cycle S3-50%
    • Down to -40 °C

Attachments

Switches for series

Switches for series

  • Contact material: Silver
  • Max. switching capacity: 6 A, 250 V AC
  • Positive-break switches (optional)
  • Gold contacts for switching smallest loads (optional)

Allgemein:

  • All switch contacts routed to terminals
  • Switching angles infinitely adjustable by means of cams
  • Retrofit switch sets available
  • Changeover contact (SPDT)

For actuators: N, NV, NE, K, KA, V

More

JNO

JNO

  • Adjustable cam that can be adjusted from above, consisting of brass body and plastic cam ring
  • Different cam shapes available

For actuators: N, K, KA, V, NV, NEx

Download Datasheet

More

JNS

JNS

  • Adjustable cam that can be adjusted from the side, consisting of plastic body and plastic cam ring
  • Grub screw ensures cam is reliably secured to the shaft
  • Different cam shapes available

For actuators: N, K, KA, V, NV, NEx

Download Datasheet

More

Electronic position controller ESR-N

Electronic position controller ESR-N

Built-in version: N, NV, K ,KA,V, NEx
External version in device base (for mounting onto standard 35 mm mounting rails)

  • Industrial-standard multilayer PCB
  • EMC tested PCB layout
  • Control electronics internally fused
  • Relay output stage with RC snubber circuit across relay contacts for motor control
  • 12 bit setpoint value input
  • 12 bit actual value output
More